Earth-Leakage Circuit Breaker (Electronic Adjustable)

Earth-Leakage Circuit Breaker
ZLM30LRE-100
ZLM30LRE-250
ZLM30LRE-400
ZLM30LRE-630
Earth-Leakage Circuit Breaker (Electronic Adjustable)

Earth-Leakage Circuit Breaker (Electronic Adjustable)

Characteristics of Earth-Leakage Circuit Breaker (Electronic Adjustable)
1. ZLM30REL earth-leakage circuit breaker (electronic adjustable) is usually used in low voltage distribution network of AC 50Hz, rated working voltage up to 690V, and rated working current up to 800A.
2. This series of earth-leakage circuit breaker can be designed with under-voltage trip, shunt trip, auxiliary switch motor operated mechanism and rotary handle, etc.
3. Our earth-leakage circuit breaker (electronic adjustable) can offer long time overload protection, short time short circuit and instantaneous short circuit protection, provided that users have set parameters of protection function with DIP switch.
4. Besides, ZLM30REL series breaker also has many other functions, such as residual current protection, ground-fault protection, thermal simulation protection, over current indication, load current indication, digital current analysis, among others.

Specifications of Earth-Leakage Circuit Breaker (Electronic Adjustable)

Frame(A) 100 250 400 630
Type ZLM30REL-100 ZLM30REL-250 ZLM30REL-400 ZLM30REL-630
Power supply system 33W,12W,13W 34W, 33W,13W,12W 33W,12W,13W 33W,12W,13W,34W
Rated current In (A) 16-32,32-63,63-100 125-250 200-400 300-630
Number of poles 3 4 3 4 3 4 3 4
Rated voltage Ue (V) AC400V AC400V AC400V AC400V
Rated insulation voltage Ui (V) AC690V AC690V AC690V AC690V
High speed type Rated current sensitivity(mA) 30,100,300 Adjustable 30,100,300 Adjustable 30,100,300 Adjustable 30,100,300 Adjustable
Max. operating time(s) 0.1 0.1 0.1 0.1
Time delay type Rated current sensitivity(mA) 30,100,300 Adjustable 30,100,300 Adjustable 30,100,300 Adjustable 30,100,300 Adjustable
Max. operating time under 21△n(s) 0.45,1.0,2.0 Adjustable 0.45,1.0,2.0 Adjustable 0.45,1.0,2.0 Adjustable 0.45,1.0,2.0 Adjustable
Inertial non-operating time (S) 0.1,0.5,1.0 0.1,0.5,1.0 0.1,0.5,1.0 0.1,0.5,1.0
Earth-leakage indication system   Button Button Button Button
Interrupting capacity Icu/Ics AC400V 80/50 80/50 70/70 70/70
Operation life (cycle) ON 1500 1000 1000 1000
OFF 7000 70000 4000 4000
Dimensions (mm)
a 105 140 105 140 140 185 210 285
b 165 165 257 257
c 91 91 103 103
ca 115 115 155 155
Weight (kg) 2 2.5 2 2.5 6.6 8.4 2.5 17.5
Electrical-operation device (MD)
External rotary handle
Automatic tripping device Electronic